20, 35 kV closed switchgear

Switchgear are designed for:

  • receiving and distributing of 3-phase AC power (50 Hz) at power facilities, oil and gas industry and other objects with  resonant earthed or isolated neutral;
  • placement of switching devices, busbars and connecting buses, auxiliary devices, as well as protection devices, automation, supervisory control, communications and measuring devices.

The switchgear is manufactured in a general purpose industrial version and is used as switchgear for indoor and outdoor installation in accordance with the requirements of technical conditions БКЖИ.670221.004TU.

Detailed information

Operating conditions

Switchgear comply with the requirements of the Electrical Installation Code, GOST 14693-90, technical conditions approved in accordance with the established procedure, customer design documentation, a package of engineering drawings, and diagrams of main and auxiliary circuits.

Switchgear designed for export must comply with the order form for foreign trade organization.

Nominal values of environmental climatic factors are as per GOST 15150-69 and GOST 15543.1, and:

  • altitude above sea level should not exceed 1000 m;

  • explosion- and fire-proof environment, free from conductive or abrasive dust, conductive or chemically active gases, vapors and sediments that destroy insulation and metals (atmosphere of type I according to GOST 15150-69);
  • ambient air temperature for outdoor heat-insulated switchgear - from -60 °С to +40 °С;
  • relative humidity is up to 80%.

Outdoor switchgear shell structure:

a) corresponds to SNiP 2.01.07 and withstands:

  • air pressure of at least 0.5 kPa;

  • weight of snow cover per 1 m² of horizontal roof surface is not less than 3.3 kPa at a safety factor of 1.0;
  • uniform load over the floor is at least 2.0 kPa.

b)provides protection of interior spaces from precipitation (intensity of up to 5 mm/min);

c) ensures operation of equipment in icy conditions at an ice thickness up to 20 mm and wind speed up to 34 m/s, and in the absence of ice - at wind speed up to 40 m/s.

Maximum seismic resistance of switchgear is six points according to SNiP II-7-81. At the customer's request, the company can manufacture switchgear with seismic resistance of up to nine points. In this case, the equipment used for the certain configuration of the switchgear must comply with the seismic resistance requirements specified in the design documentation.

Switchgear do not resist shaking and vibration, and cannot be used in mobile, mine and other stations.

Main parameters and characteristics

Parameter name

Parameter value

On the HV side

 

Maximum capacity, kVA:

 

of indoor transformers

of outdoor transformers

2500

16000

Number of power transformers

1, 2

Rated voltage (line voltage), kV

20, 35

Highest operating voltage (line voltage), kV

24, 40,5

Test voltage of electrical equipment of switchgear in dry condition for one minute in accordance with the requirements of GOST 1516.3, kV

 

- on the ground

50/65 1) , 80/95 1)

- of power transformers relative to ground

50/55 1) , 80/85 1)

- between the contacts of the fuse disconnectors

60/75 1) , 95/120 1)

Test voltage of insulation of auxiliary circuits during 1 min in accordance with GOST 1516.3, kV

2

Rated current of main circuits of switchgear cabinets, A

630, 1000, 1600, 2000, 2500

Rated current of busbars, A

1000, 1600, 2000, 2500, 3150

Rated tripping current of the switchboard built-in circuit breaker, kA

12,5; 16; 20; 25; 31,5, 40

Thermal resistance current (during 3 s), kA

20, 25, 31,5, 40

Rated current of electrodynamic resistance of main circuits of switchgear cabinets (amplitude), kA

51, 64, 81, 102

On the medium voltage (MV) side of (CTS-35 (20)/6(10) kV

 

Rated voltage, kV

6; 10

Highest operating voltage, kV

7,2; 12

Rated current of busbars, A

630; 1000; 1600; 2000; 2500; 3150; 4000

Electrodynamic resistance current of the busbar, kA

51; 64; 81; 102; 128

Thermal resistance current, kA

20; 25; 31,5; 40; 50

Thermal resistance current flow time, s

3

Rated voltage, V

 

of auxiliary DC circuits

of AC auxiliary circuits

110; 220

220

On the LV side of CTS-35/0.4 kV

 

Rated voltage, kV

0,4

Rated current, A

400; 630; 1000; 1600; 2000; 2500; 4000; 5000

Electrodynamic resistance current of the busbar, kA

21; 38; 51; 81; 100

Thermal resistance current, kA

10; 18; 22; 40; 50

Thermal resistance current flow time, s

1

1) The numerator shows values for level “a” insulation, the denominator shows values for level “b” insulation.

Classification of switchgear designs

Name of classification indicator

Execution

Insulation level according to GOST 1516.3-96

a, b

Type of insulation

Air,
combined

Наличие изоляции токоведущих шин главных цепей

With insulated busbars;
with uninsulated busbars;
with partially insulated busbars

Система сборных шин

With top-mounted busbars
With lower busbar arrangement

Presence of pull-out elements in cabinets

With pull-out elements;
without trolley elements;
with cassette-type trolley elements

Type of linear high-voltage connections

Cable;
overhead lines;
busbars

Maintenance conditions for high-voltage cells

Two-way service;
single-sided

Protection degree of shells according to GOST 14254-96

Not lower than IP20 - for indoor switchgears,
IP23 - for outdoor switchgears with open ventilation grilles,

Type of auxiliary equipment and apparatus

Cabinets with operating current sources and rectifying devices,
relay protection,
control automation circuits, signaling and communication circuits, etc.

By mutual arrangement of high-voltage equipment

Single-row;
double-row

According to the method of outgoing line outputs execution (busbars and cables)

Lead up;
output down;
up and down outputs

Type of main enclosures depending on installed equipment and connections

With high-voltage vacuum circuit breakers;
with disconnectors;
with fuses;
with voltage transformers;
with auxiliary transformers;
with auxiliary equipment;

with non-linear surge arresters;
with busbar entries from above;
with high-voltage circuit breakers and voltage transformers;
with cable glands from below.

By type of shells (block module for outdoor switchgear substations)

In insulated sheathing;
uninsulated sheathing

Type of control

Local;
remote;
local and remote

By number of modular units

Single-module;
multimodular

According to the arrangement of cell busbars

Upper,
lower

Requirements to reliability

Switchgear meets the requirements for reliability and durability in accordance with GOST 20.39.312-85.

Outdoor switchgear ensure continuous operation of engineering equipment while unattended.

The established service life of the switchgear is not less than 25 years, subject to maintenance or replacement of equipment, in accordance with the instructions of the operation manual for certain types and their components (when replacing components whose service life is less than 25 years).

Reliability indicators of the main equipment (mean time between failures, probability of failure-free operation, etc.) - in accordance with the requirements of the technical conditions for the installed equipment.

Maintenance of the installed equipment and its repair are carried out using the spare parts kit supplied together with the equipment.

Product components

The switchgear a set of separate cabinets including switching devices and other high-voltage components, measuring instruments, automation and protection devices, as well as control and signaling equipment and other auxiliary devices. The cabinets are connected to each other in accordance with the electrical diagram according to the data sheet.

The configuration of switchgear equipment is determined by the customer and project design and usually includes:

  • a set of high-voltage equipment;
  • AC or DC power supply and distribution switchboards for power supply of auxiliary operative circuits.

 Outdoor switchgear additionally include:

  • pre-fabricated modular building;
  • HVAC and lightning;
  • security and fire alarm.

The technical characteristics of the equipment and components installed in the switchgear meet the requirements of the relevant standards and technical conditions of the manufacturers.

Single-line electrical diagrams of the main switchgear circuits must correspond to the project design, and in case of production according to non-standard diagrams - to the customer's diagrams.

A set of high voltage equipment consists of:

  • switchgear - switchgear cabinets;
  • busbar or cable bridges for connecting cubicles in double-row switchgear designs;
  • other auxiliary equipment at customer's request.

The number of modular units of outdoor switchgears depends on the amount of equipment built into it.

The type of the installed equipment and its configuration are determined by the customer and project design.

The type of the used communications and supervisory control devices (if any) is determined by the customer and project design.

Auxiliary equipment for outdoor switchgear

The equipment for maintaining microclimate generally includes the following components:

  • auxiliary box;
  • heaters (convectors with mechanical thermostat or radiant heaters). The room temperature is regulated by thermostats operating in the range of -10…+50 °C;
  • air temperature sensor (fan thermostat);
  • electric fans;
  • air conditioning system with control device (the type of air conditioner is determined by the customer and project design).

At the customer's request, it is possible to install other types of equipment for microclimate maintenance.

Internal workspace lighting is provided by fluorescent lamps, unless otherwise specified in the project specification.

Outdoor lighting is provided by incandescent lamps.

Working lightning voltage is ~220 V.

According to the requirements of SNiP 23-05-95, emergency and backup lighting of evacuation exits from a switchgear module is equipped with emergency luminaires LBA, installed at the entrance doors of switchgear, which indicate to a person a way to a safe place and ensure continuous operation for three hours in case of power failure.

Emergency lighting inside the switchgear, if there is an operating current cabinet SHOTV, is carried out by luminaires with incandescent lamps.

There is a step-down transformer ~220/12 V in the auxiliary box for maintenance lighting.

Security and fire alarm equipment (perimeter alarm system) generally includes:

  • balanced magnetic switches (magnetic contact security alarm or contact switches);
  • intruder detectors (space violation detectors);
  • optoelectronic fire detectors (smoke fire detectors).

Upon the customer request, it is possible to install other types of security and fire alarm equipment, including in a separate box.