Single-end service assembled chamber CSR 306, 306 SHVV series

Chambers CSR-360 are designed for receiving and distributing of 3-phase AC power (50/60 Hz) at 6 and 10 kV power facilities with resonant earthed or isolated neutral.

Chambers CSR-306 SHVV are designed to provide high-voltage bushing for various facilities of 6 and 10 kV.

Climatic version - N and T, location category - 3 as per GOST 15150. Nominal values of environmental climatic factors are as per GOST 15150 and GOST 15543.1 And:

  • ambient temperature - from -45 to +40°С;
  • altitude above sea level should not exceed 1000 m;
  • seismic resistance according to MSK 64 scale - up to 9 points;
  • explosion-proof environment, free from conductive dust, aggressive vapors and gases that destroy insulation and metals.

Detailed information

Main parameters and characteristics

  CSR-306 CSR-306 SHVV
Rated voltage (line voltage), kV 6; 10 6; 10
Rated operating voltage (line voltage), kV 7,2; 12 7,2; 12
Rated current of main circuits, A 400; 630 400; 630
Rated tripping current, A 630 630
Thermal resistance current (three-second current), kA 20 20
Rated current of electrodynamic resistance, kA 51 51
Rated current of current transformers, A 50; 75; 100; 150; 200; 300; 400; 600 -
Rated current of busbars, A 630 -
Rated current of busbar bridges, A 630 -
Rated voltage of auxiliary circuits, V: 220;380 220;380
Lighting circuits inside the CSR chamber, V 36; 220 36; 220
Fuse insert current of the power fuse, A 2; 3,2; 5; 8; 10; 16; 20; 31,5 + 160;200 
Insulation level according to GOST 1516.1 With normal insulation 
Presence of insulation of main circuit busbars With uninsulated busbars 
Busbar system With one busbar system 
Type of linear high-voltage bushings (connections) Cable and busbars
Degree of protection according to GOST 14254

IP20 - for the outer shells of the facade and sides;

IP30 - for the side walls of the outermost chambers in the row;

IP00 - for the rest of the chambers

Note - Thermal and electrodynamic resistance of current transformers according to their technical parameters.

Design

The devices, instruments, current-carrying parts, isolation barrels, fasteners, and supporting structures used in the CSR chambers are selected and installed so that gases or oil emitted from the devices cannot cause harm to service personnel and do not cause sparkovers of the CSR chamber insulation . The CSR chamber has viewing windows on the front side to monitor the position of the switching devices

Each chamber is equipped with interior lampholder with the ability to safely replace burnt-out lamps without removing voltage from the main and auxiliary circuits. Sockets for portable lamps and interior lamp switch are installed on the front part of the chambers

The doors of the CSR chambers are locked with keys

The following mechanical interlocks are provided in the CSR chambers:

  • interlock preventing the opening of the CSR chamber doors when the load switch is on;

  • interlock preventing the opening of the CSR chamber doors when the earthing switches are shut off;
  • interlock preventing the earthing switches from being switched on when the disconnectors switches and load switches are on;
  • interlock preventing disconnectors from being switched on when earthing switches are on.

For other types of interlocks (operational safety, etc.) in accordance with the auxiliary circuit diagrams, block locks and limit earthing position switches (optional) can be installed in the CSR chambers

The CSR-306 chambers can be connected to other types of chambers (CSR 300) using socket adapters

Main busbars of the CSR chambers, located in two rows facing each other (Fig. 2.4, 2.5) are connected by busbar bridges or cable connections (busbar bridges are supplied upon request). The length of the busbar bridges is disigned for placement of the CSR chambers, the passage width between the chambers: 2000; 2500; 3000 mm.

Busbar bridges are manufactured both with and without disconnectors. The control drives for the disconnectors are placed on special panels.