Electromagnetic contactors KE16 series
ТУ3426-161-00216823-2006
KE16 low-voltage electromagnetic contactors are intended for switching loads up to 660 V AC, frequency 50 and 400 Hz, including control of squirrel-cage induction motors.
Contactors can be used in various environmental conditions and are highly reliable.
Main features
| Electrical durability, cycles | 500000 |
| Mechanical durability, CO cycles | 2 mln. |
| Switching frequency: | |
| - KE16-010ХХХV3 | 1200 |
| - КE16-025ХХХV3 | 1200 |
| - КE16-063ХХХV3 | 1200 |
| - КE16-100ХХХV3 | 600 |
| Make time, not more, s | 0,6 |
| Break time | |
| - AC control circuit, not more, s | 0,4 |
| - DC or rectified current control circuit, not more, s | 0,1 |
| Protection level | IP00 |
| Protection level of main and control circuit contacts | IP20 |
| Climatic modification according to GOST 15150 | В3 |
| Service life, years | 25 |
Electrical durability, cycles 500000 Mechanical durability, CO cycles 2 mln. Switching frequency: - KE16-010ХХХV3 1200 - КE16-025ХХХV3 1200 - КE16-063ХХХV3 1200 - КE16-100ХХХV3 600 Make time, not more, s 0,6 Break time - AC control circuit, not more, s 0,4 - DC or rectified current control circuit, not more, s 0,1 Protection level IP00 Protection level of main and control circuit contacts IP20 Climatic modification according to GOST 15150 В3 Service life, years 25
Technical Data
| Type | Rated current, А | Number and type of contacts | Rated voltage of control circuit, V | |||
| main | auxiliary | DC | rectified | AC | ||
| КE16-010Х0V3 | 10 | 3 NO | 1 NO+1 NC | 24, 110, 220, 27 | 57, 99, 171 | 127, 220, 380 |
| КE16-010Х1V3 | 2 NO | |||||
| КE16-010Х7V3 | 2 NO+ 1 NC | 1 NO + 1 NC* | ||||
| КE16-025Х5V3 | 25 | 3 NO | 2 NO+2 NC | |||
| КE16-025Х6V3 | 4 NO | |||||
| КE16-063Х3V3 | 63 | 3 NO+1NC | ||||
| КE16-063Х4V3 | 3 NO+2 NC | |||||
| КE16-063Х5V3 | 2 NO+2 NC | |||||
| КE16-100Х3V3 | 100 | 3 NO+1 NC | ||||
| КE16-100Х4V3 | 3 NO+2 NC | |||||
| КE16-100Х5V3 | 2 NO+2 NC | |||||
* Auxiliary contact for rated current of 10 А, rated voltage of 24 V DC or 220 V AC without inductive load.
Х – rated voltage of control circuit: 1 – 127 V AC, 2 – 220 V AC, 3 – 380 V AC, 4 – 57 V rectified, 5 – 99 V rectified, 6 – 171 V rectified, 7 – 24 V DC, 8 – 110 V DC, 9 – 220 V DC, 0 –27 V DC.
Rated current of auxiliary contacts – 6.3 А
| Contactor type | Weight, kg |
| КE16-010 | 1.1 max. |
| КE16-025 | 1.6 max. |
| КE16-063 | 3.2 max. |
| КE16-100 | 6.2 max. |